Comparative Study of Short-Circuit Current Contribution from  
Small Hydropower and DFIG Wind Generators in Power Systems  
Doan Kim Tuan  
Electrical Faculty, Thai Nguyen University of Technology, Thai Nguyen, Viet Nam  
Corresponding Author  
Received: 02 November 2025; Accepted: 10 November 2025; Published: 21 November 2025  
ABSTRACT  
This paper presents a method for calculating and simulating short-circuit currents in power systems with the  
simultaneous participation of small hydropower generators and wind power generators based on doubly fed  
induction machines. Based on detailed modeling of the control structure and power electronic converters,  
different short-circuit scenarios were established to evaluate the current response of the two generation sources.  
The simulation results show that the short-circuit current of small hydropower generators exhibits a high initial  
magnitude and decreases according to the subtransient, transient, and steady-state characteristics. In contrast, the  
short-circuit current of wind generators using doubly fed induction machines is limited by the converters and  
protection mechanisms, and is strongly influenced by the applied control strategies. The analysis and comparison  
of these two generation types accurately reflect the power distribution and current variations in the system during  
short-circuit conditions. The research results provide an important basis for protection design, reliability  
assessment, and stable operation of power systems integrating small hydropower and wind energy sources.  
Index TermsDFIG, Control structure, Renewable energy, Short-circuit calculation, Small hydro power plant.  
INTRODUCTION  
In power system analysis, the calculation and prediction of short-circuit currents play a particularly important  
role in equipment selection, protection design, and reliability assessment. With today’s diverse generation mix,  
ranging from small hydropower plants to wind turbines employing doubly fed induction generators (DFIG), the  
characteristics of short-circuit currents have become increasingly complex, requiring specialized analytical  
methods.  
For small hydropower generators, short-circuit currents usually consist of subtransient, transient, and steady-  
state stages, and are significantly affected by the machine reactances, excitation system parameters, and  
hydraulic characteristics. Studies have shown that constant switching phenomena and arc voltages during faults  
must be taken into account to accurately calculate short-circuit currents in hydropower units [3], [4]. In addition,  
local short-circuit conditions such as inter-turn faults in the stator winding of small hydropower generators are  
of concern due to their direct impact on equipment safety and lifespan [7]. Furthermore, recent research has  
analyzed the phenomenon of “hydraulic short-circuit” in hydropower systems, showing that the coupling of  
hydraulic and electrical processes can lead to highly complex transient behavior [10].  
In contrast, the short-circuit response of DFIG-based wind turbines is governed by power electronic converters  
and protection mechanisms. During faults, DFIGs may sustain or limit current contributions depending on  
control strategies, reactive power support modes, and the activation of the crowbar circuit [1], [2], [5], [8], [9].  
Recent works have developed detailed short-circuit models for DFIGs, considering coordinated control between  
the rotor-side and grid-side converters [2], as well as the influence of reactive power support strategies on short-  
circuit current calculations [8]. In particular, new calculation methods have improved the accuracy of short-  
circuit current prediction for DFIGs, thereby enhancing fault analysis and protection design in power systems  
[1], [5].  
Page 2081  
In the context of power systems increasingly integrating both small hydropower and DFIG-based wind power,  
the comparative analysis of short-circuit currents and current responses from these two sources has become  
essential. This not only supports the development of accurate simulation models but also directly contributes to  
protection design, operation planning, and improving the reliability of modern power grids [3][10].  
Based on these considerations, this paper focuses on the system structures of DFIG-based wind turbines and  
small hydropower generators, and their responses under short-circuit conditions. The next section introduces the  
control structures of DFIGs and small hydropower generators, together with the short-circuit current calculation  
methods. Section III provides analyses of the responses of DFIGs and small hydropower units under short-circuit  
faults, including both transient and sustained cases. The final section presents the conclusions and main findings  
of the study.  
STRUCTURE OF DFIG SYSTEM, SMALL HYDROPOWER, AND SHORT-CIRCUIT  
CALCULATION METHOD IN POWER SYSTEMS  
Control Structure of DFIG-Based Wind Power System  
The control structure of a wind power generator using a doubly fed induction generator is established based on  
the integration of two power electronic converters, namely the rotor-side converter (RSC) and the grid-side  
converter (GSC), as illustrated in Fig. 1. The rotor-side converter is responsible for controlling the rotor current  
in the ddd-qqq reference frame, thereby regulating the active and reactive power output of the generator. The grid-  
side converter ensures a stable DC-link voltage and simultaneously regulates the current exchanged with the  
power grid [1], [2].  
Under normal operating conditions, the rotor-side control system is typically designed using either stator flux  
orientation (SFO) or grid voltage orientation (GVO), which allows the decoupling of active and reactive power  
control. Consequently, the DFIG can flexibly meet power dispatch requirements and participate in voltage  
regulation at the point of common coupling [2], [5].  
Filter  
Gearbox  
Grid  
igrid  
Rotational  
speed  
ugrid  
DC voltage controller,  
Current controller,  
Grid synchronization  
Current  
controller  
Pitch  
angle  
iref  
Control  
operation  
Power/Speed  
control  
Pmea, Qmea  
Fig.1 Control structure of DFIG  
When a short-circuit occurs in the grid, the short-circuit current characteristics of the DFIG strongly depend on  
this control structure. If the converters can maintain continuous excitation, the short-circuit current can be limited  
to a desired level while simultaneously providing reactive power support to the grid [1]. In severe fault conditions,  
the crowbar protection mechanism is triggered to protect the converters, which alters the fault current  
characteristics and causes a temporary reduction in controllability. In addition, advanced control strategies, such  
as emergency reactive power support, have been proposed to improve low-voltage ride-through capability and  
enhance system stability [8].  
Thus, the control structure of the DFIG not only determines the efficiency of operation under normal conditions  
but also directly influences the current response during short-circuits, playing a key role in fault modeling and  
short-circuit current calculations.  
Page 2082  
Máy phát thủy đin  
The small hydropower generator is a synchronous machine, in which the control system plays a crucial role in  
maintaining terminal voltage and output power during both normal operation and fault conditions. The Automatic  
Voltage Regulator (AVR) is responsible for keeping the generator terminal voltage stable by controlling the field  
current. During short-circuits, the AVR responds rapidly by increasing the excitation current to compensate for  
the voltage drop, which directly affects the short-circuit current characteristics in the transient stage [3], [4].  
In parallel, the Governor regulates the water flow into the turbine, ensuring the balance between mechanical input  
and electrical output power. In the event of a short-circuit or sudden load change, the Governor responds more  
slowly than the AVR but is essential for maintaining frequency stability and power output [6]. Furthermore, in  
systems with stringent stability requirements, a Power System Stabilizer (PSS) can be integrated to provide  
supplementary signals, helping to damp oscillations and improve the dynamic stability of small hydropower  
generators [10].  
Several studies have also shown that the coordination of AVR, Governor, and PSS significantly influences the  
transient response of small hydropower generators under fault conditions. For example, during a three-phase  
short-circuit, the initial current is mainly governed by the machine parameters, while the recovery of voltage and  
frequency stability largely depends on the control system [6], [7], [10]. In small hydropower plants, the generators  
are integrated into the grid as illustrated in Fig. 3.  
Generator  
Generation  
Grid and electric loads  
Grid structure  
Monitoring  
system  
Setpoint adjustment  
(tilt, hinge)  
Speed converter  
Shaft speed measuring  
device (tachometer)  
Hydraulic  
motor  
Speed  
sensor  
Controller  
Hydraulic actuator  
control  
Feedback signal  
Generator  
speed  
signal  
Frequency  
signal  
Flow  
control in  
penstock  
Grid  
Water gate  
control  
~
Turbine  
Generator  
Control structure  
Fig.2 Control structure of small hydropower generator  
Short-Circuit Calculation Method in Power Systems  
Depending on the type of short-circuit, the equivalent circuit diagrams are established using the Thevenin  
equivalent voltage source at the fault location, as illustrated in the figures below [1][6]. In these diagrams, the  
notation F(3) represents a three-phase short-circuit, F(2) denotes a line-to-line short-circuit, F(1,1) indicates a double  
line-to-ground short-circuit, and F(1) corresponds to a single line-to-ground short-circuit.  
Page 2083  
Fig.3 Equivalent circuit for short-circuit calculation  
For a three-phase short-circuit: the subtransient short-circuit current and peak short-circuit current at the fault  
location are given by:  
cUn  
cUn  
3 Rk2 Xk2  
Ik"   
(1)  
3Zk  
ip kp 2Ik"  
(2)  
where: kp is the peak factor; c is the coefficient corresponding to the type of power network; Un is the norminal  
voltage of the network; Rk and Xk are the resistance and reactance up to the short-circuit location.  
For a line-to-line short-circuit [1][6]: In the initial stage of the short-circuit current, the negative-sequence  
impedance is approximately equal to the positive-sequence impedance. The subtransient short-circuit current  
and peak short-circuit current at the fault location are given by:  
cUn  
cUn  
3
Ik"2  
Ik"  
(3)  
2
Z(1) Z(2) 2 Z(1)  
ip2 kp 2Ik"2  
(4)  
where: Z(1) and Z(2) are the positive-sequence and negative-sequence impedances up to the short-circuit location.  
For a double line-to-ground short-circuit [1][6]: In the initial stage of the short-circuit current, the negative-  
sequence impedance is approximately equal to the positive-sequence impedance. If  
, the short-circuit  
Z(2) Z(1)  
currents in phases B and C are given by:  
Z(0) / Z(1) a  
Ik"2Eb cUn  
(5)  
(6)  
Z(1) 2Z(0)  
Z(0) / Z(1) a2  
Ik"2Ec cUn  
Z(1) 2Z(0)  
Page 2084  
where: is the rotation operator; Z is the zero-sequence impedance up to the short-circuit location.  
a
(0)  
The subtransient short-circuit current and peak short-circuit current at the fault location are given by:  
(7)  
3cUn  
  
I
kE 2E  
Z(1) 2Z(0)  
ip2E kp 2Ik"2E  
(8)  
- For a single line-to-ground short-circuit:  
If  
, the total subtransient short-circuit current and peak short-circuit current at the fault location are  
Z(2) Z(1)  
given by:  
3cUn  
Ik"1  
(9)  
2Z(1) Z(0)  
ixk1 kxk 2Ik"1  
(10)  
IMPACT OF DFIG AND SMALL HYDROPOWER ON SHORT-CIRCUIT CURRENTS  
IMPACT OF DFIG ON SHORT-CIRCUIT CURRENTS  
Wind generators employing doubly fed induction generators (DFIGs) exhibit short-circuit behavior that is  
fundamentally different from synchronous generators. During a fault, the short-circuit current of the DFIG is  
directly governed by the control structure and the load capability of the power electronic converters, rather than  
being solely dependent on the machine reactances. Several studies have demonstrated that accurate modeling of  
DFIG short-circuit currents requires consideration of coordinated control between the rotor-side converter (RSC)  
and grid-side converter (GSC), which allows the fault current characteristics to be correctly represented [1], [2].  
Under normal conditions, the rotor-side controller can maintain continuous excitation and provide reactive power  
support to the grid during a fault, thereby improving voltage recovery [1], [5]. However, under more severe  
faults, the crowbar protection circuit is activated to safeguard the converters, causing the DFIG to temporarily  
operate as a squirrel-cage induction generator and thus altering its short-circuit current characteristics [9]. In  
addition, advanced emergency reactive power support strategies have been proposed to enhance low-voltage  
ride-through capability, thereby contributing to improved system voltage stability [8].  
Therefore, the short-circuit current of a DFIG is not only the result of electromagnetic phenomena within the  
machine but also the outcome of complex interactions between hardware and control structures. Modern models  
and calculation methods must therefore integrate the influence of power electronic control systems to accurately  
reflect the behavior of wind power sources under fault conditions [2], [5], [8].  
When a short-circuit occurs in the power system, the response of the DFIG can be described as follows:  
Short-term response in the initial transient stage: The grid voltage drops due to the direct stator connection. This  
leads to large transient currents in both the stator and rotor during the first few cycles. The RSC and GSC are  
designed to limit the current (typically 1.11.2 p.u.). If the current exceeds this threshold, the crowbar circuit is  
activated, shorting the rotor through a resistor and causing the DFIG to behave like a conventional induction  
generator [1], [2], [9].  
Long-term response: After crowbar activation, the DFIG contributes a decaying short-circuit current over time  
due to its induction characteristics, with the AC component gradually diminishing [5], [8].  
Thus, the short-circuit current contribution of a DFIG follows two scenarios: (i) when the converters limit the  
current, the short-circuit current contribution remains small; (ii) when the crowbar is activated, the DFIG  
Page 2085  
contributes a significant short-circuit current similar to an induction generator. The peak current can reach 46  
p.u immediately after the fault, but this decays over time, typically reducing to about 1.21.5 p.u after a few  
cycles. The contribution of short-circuit current is illustrated in Fig. 4 [2], [9].  
a. Instantaneous short-circuit current  
b. Amplitude envelope of short-circuit current  
c. Decaying DC Offset Components  
Fig.4 Illustration of short-circuit current contribution of DFIG  
Fig. 4a: The instantaneous waveform I(t)I(t)I(t) over the time interval (040 ms) is shown for two scenarios:  
converter-limited and crowbar activation.  
Fig. 4b: The variation of the current magnitude in the crowbar scenario compared with the converter-limited  
case.  
Fig. 4c: The decay of the DC offset component over time for both scenarios.  
The plots in Fig. 4 indicate that: the large initial peak followed by a decay represents induction generator-like  
behavior when the crowbar is triggered; the initial magnitude in this example is approximately 5 p.u, decaying  
to about 1.5 p.u (parameters can be adjusted according to actual system data). The DC offset component causes  
asymmetry in the fault current waveform and decays with a time constant, playing a major role in the peak  
current IpI_pIp during the first few cycles. In the converter-limited case, the current is approximately equal to  
the set limit (~1.2 p.u) with very little DC offset.  
In the converter-limited mode, the current at the fault location is determined as follows [2], [9]:  
IF=Igrid+IDFIG  
(11)  
Since the DFIG current is limited to Iconv_max, the fault current can be further expressed with a phase angle. If the  
phase angle is unknown, the DFIG contribution is considered only by its magnitude, IDFIG=Imax. In this case, the  
short-circuit current is determined similarly to the formulas presented in Section II.  
Page 2086  
When the crowbar is engaged, the DFIG is modeled as an internal voltage source EDFIG (≈Uph) with an internal  
impedance ZDFIG (ypically represented as jX"m+ Rcrowbar). The short-circuit current at the fault location is then  
determined as follows [2], [9]:  
Egrid  
Zgrid _to_ fault ZDFIG _to_ fault  
EDFIG  
Ik" Igrid IDFIG  
(12)  
(Usually, Egrid≈Uph, EDFIG≈Uph if the synchronous/induction machine internal voltage is equivalent to the phase  
voltage).  
(1)  
The DFIG under crowbar protection can be represented with components ZDFIG và ZDFIG(2); zero-sequence  
impedance ZDFIG(0) is typically zero or very small (depending on rotor/neutral grounding). When applying phase-  
to-ground or phase-to-phase short-circuit calculation formulas, the DFIG impedance should be added into the  
corresponding Z(1) and Z(2).  
Impact of Hydro Generators on Short-Circuit Current  
When a short circuit occurs, the generator terminal voltage drops abruptly, approaching zero at the fault location  
(if the fault is close to the generator). The generator current surges to the initial short-circuit current, whose  
magnitude depends on the machine time constants and internal reactances. The short-circuit current of the  
generator decays over time with distinct stages:  
Subtransient stage: subtransient current (first few cycles, very high due to the small subtransient reactance X"d  
);  
Transient stage: transient current (decays more slowly, governed by the larger transient reactance X’d);  
Steady-state stage: steady-state fault current (much lower, limited by the synchronous reactance Xd).  
Therefore, a hydro generator contributes a very large current in the first few cycles following the fault, which  
may reach 57 times the rated current [3].  
Due to electromechanical and governor dynamics, the terminal voltage decreases while the fault current remains  
high. This causes the electromagnetic torque of the generator to drop sharply, whereas the mechanical torque  
from the water turbine remains unchanged in the short term. As a result, the generator accelerates (rotor angle δ  
increases). This behavior can be addressed by the block diagram representing the generator control system  
response, as shown in Fig. 5 [4], [6], [7].  
Short circuit  
(at power  
system or grid)  
Automatic  
Voltage Regulator  
(AVR)  
Synchronous  
Generator (Fault  
current)  
Terminal  
voltage drop  
Governor  
(Mechanical  
Control)  
Power System  
Stabilizer (PSS if  
having)  
Fig.5 Generator control response during short circuit  
The AVR/Exciter receives the input signal (voltage reference) and compares it with the terminal voltage  
feedback from the generator, then adjusts the excitation accordingly. The synchronous generator contributes to  
the short-circuit current, leading to a terminal voltage drop and changes in power/speed. The governor receives  
the power/speed feedback from the generator and regulates the mechanical input (hydraulic turbine). The PSS  
(Power System Stabilizer) processes the power oscillation signals from the generator and provides a stabilizing  
signal back to the AVR.  
If the fault is prolonged, the short circuit may cause loss of synchronism with the grid. The governor, due to its  
inertia and slow response, cannot immediately adjust the water flow into the turbine [4], [6], [7].  
Page 2087  
If the fault is cleared quickly (within a few cycles), the generator can remain synchronized and restore its  
terminal voltage. However, if the fault persists or is cleared too slowly, there is a risk of rotor angle instability  
and generator disconnection from the system. The fault current waveform contributed by the hydro generator is  
illustrated in Fig. 5 [4], [6], [7].  
Fig.6 Fault current waveform of the hydro generator  
In this figure: the blue curve represents the total short-circuit current, consisting of an AC component with  
decaying amplitude and a DC offset component that gradually diminishes. The red dashed curve shows the  
maximum and minimum envelope of the voltage/current waveform over time.  
Accordingly, the fault current exhibits a strong DC offset and very high magnitude during the first few cycles.  
Then, the oscillations gradually decay toward the steady-state level. In the subtransient stage, the current is  
extremely large immediately after the fault (≈ 5–7 times the rated current), followed by a very rapid decay within  
the first few cycles. In the transient stage, the current remains above the rated value but decreases more slowly,  
governed by the transient time constant. In the steady-state stage, the current settles to a smaller value after a  
long duration (≈ 1.1–1.2 times the norminal current).  
For short-circuit calculations, the hydro generator is modeled as an internal emf source E′′≈10° p.u in series  
with the subtransient reactance X"d. Since the hydro generator has the same electrical characteristics as a  
conventional synchronous generator, the three-phase synchronous machine model can be applied. Typically, the  
subtransient reactance X"d is used in fault current studies because the initial stage of the fault current is the most  
critical.  
SIMULATION RESULTS  
In the test system, a DFIG plant is connected at Bus 6, while a hydro power plant is connected at Bus 4, as shown  
Inductor  
~
Power  
source  
Transmission  
line L1  
Bus2  
T2  
Bus1  
T1  
DFIG  
controller  
Fault  
Bus3  
M1  
M2  
S1  
Bus4  
T3  
Load 1  
Transmission  
line L2  
CB  
Hydro  
power plant  
~
Bus5  
Load 2  
DFIG Plant  
Capacitor  
bank  
Bus6  
in Fig. 7 [11].  
Fig.7 A System with the participation of DFIG and hydro power plant  
To evaluate the power distribution across the system introduced in Fig. 7, the simulation parameters are presented  
in the following tables. These parameters characterize the power sources, inductors, transformers T1, T2 and T3,  
electrical loads, the DFIG, and the transmission line L1 and L2, small hydro power plant.  
Parameters Of Power Source And Inductor  
Number  
Name of parameter  
Voltage amplitude  
Frequency  
Symbol  
Uph-ph  
f
Value  
120 kV  
60 Hz  
1
2
Page 2088  
3
4
5
6
Positive-sequence resistance of inductor  
Positive-sequence capacitance of inductor  
Zero-sequence resistance of inductor  
Zero-sequence capacitance of inductor  
R1  
L1  
R0  
L0  
0.1  
3×104 H  
0.3   
9×104 H  
Parameters of T1 transformer  
Number  
Name of parameter  
Symbol  
Sn  
Value  
1
2
3
Norminal power  
50 MVA  
Voltage ratio  
Uprimary/Usecondary 120kV/25kV  
2.67×10-3  
R
Primary and secondary winding resistance  
(p.u)  
4
Primary and secondary winding capacitance  
L
0.08 (p.u)  
Parameters of T2 transformer  
Number  
Name of parameter  
Symbol  
Srated  
Value  
1
2
3
4
Rated power  
2.5 MVA  
Voltage ratio  
Uprimary/Usecondary  
R1=R2  
25kV/2.3kV  
1.3×10-3 (pu)  
0.04 (pu)  
Primary winding resistance  
Primary winding inductance  
L1=L2  
Parameters of T3 transformer  
Number  
Name of parameter  
Symbol  
Srated  
Value  
1
2
3
Rated power  
Voltage ratio  
12 MVA  
Uprimary/Usecondary 25kV/575V  
R1=R2  
8.3×10-4 (pu)  
Primary and secondary winding  
resistance  
4
Primary winding inductance  
L1=L2  
0.025 (pu)  
Parameters of electric loads  
Number  
Name of parameter Symbol  
Value  
1
2
Load 1  
Load 2  
PLoad1+jQLoad1  
PLoad2+jQLoad2  
0,2+j0 MVA  
1+j0 MVA  
Page 2089  
Parameters of DFIG  
Number  
Name of parameter Symbol  
Value  
06  
1
2
3
4
5
6
7
8
Number of generator  
Rated power  
n
Prated  
Uph-ph  
cos  
f
1.5 MVA  
575 V  
0.9  
Rated voltage  
Power factor  
Rated frequency  
Rated wind speed  
Cut-in wind speed  
Cut-out wind speed  
60 Hz  
12 m/s  
3 m/s  
60 m/s  
vrated  
vcut-in  
vcut-in  
Parameters of transmission line  
Number  
Name of parameter Symbol  
Value  
1
2
3
4
5
6
7
Length  
L1 and L2  
L1=18 km; L2=15 km  
0.1153 /km  
0.413 /km  
Positive resistance  
Zero resistance  
Positive Inductance  
Zero Inductance  
R1  
R0  
X1  
X0  
1.05×10-3 H/km  
3.32×10-3 H/km  
11.33×10-9 F/km  
5.01×10-9 F/km  
Positive Capacitance C1  
Zero Capacitance C0  
Parameters of hydro power plant  
Number  
Name of parameter Symbol  
Value  
1
2
3
4
5
6
7
Norminal power  
Power factor  
Sn  
pf  
1.68 MVA  
0.93  
Norminal voltage  
Stator resistance  
Stator inductance  
Rotor resistance  
Rotor inductance  
Un  
R1  
L1  
R2  
L2  
2.3 kV  
0.0092 p.u  
0.0717 p.u  
0.007 p.u  
0.0717 p.u  
Page 2090  
8
9
Inertia constant  
Friction factor  
H
F
0.5 s  
0
The wind speed variation scenario is illustrated in Fig. 8.  
Fig.8 Wind speed variation scenario  
The simulation study considers three operating scenarios: (i) normal operation without faults, (ii) a temporary  
short-circuit on Line 2 near Bus 3 at 6 s lasting 0.1 s, and (iii) a sustained short-circuit on Line 2 near Bus 3 at 6  
s lasting 0.9 s.  
Simulation results for Scenario 1: Fault-free system  
The corresponding DFIG active and reactive power responses under Scenario 1 (no fault) are shown in Fig. 9.  
a. Active power  
b. Reactive power  
Fig.9 Active and reactive power output from the DFIG in Scenario 1  
The active and reactive power of the small hydro generator are illustrated in Fig. 10.  
a. Active power  
b. Reactive power  
Page 2091  
Fig.10 Active and reactive power output of the small hydro generator in Scenario 1  
a. Active power  
b. Reactive power  
Fig.11 The active and reactive power exchanged with the power source in Scenario 1  
The simulation results show that the power output from the DFIG and the hydro generator remains positive (both  
active and reactive power). Meanwhile, the active power exchanged with the grid is positive during the initial  
stage and becomes negative in the steady state, whereas the reactive power remains positive throughout. This  
indicates that both the DFIG and the hydro generator supply active power to the system while absorbing reactive  
power to maintain voltage stability. The power distribution in Scenario 1 is presented in Fig. 12.  
Inductor  
~
Power  
source  
Transmission  
line L1  
Bus2  
T2  
Bus1  
T1  
P1+jQ1  
DFIG  
controller  
Bus3  
M1  
M2  
S1  
Bus4  
T3  
Load 1  
PDFIG+jQDFIG  
Bus5  
CB  
Transmission  
line L2  
Hydro  
power plant  
~
DFIG Plant  
Capacitor  
bank  
Pplant+jQplant  
Load 2  
Bus6  
Fig.12 Power distribution in Scenario 1  
The simulation results of current exchanged with the grid are shown in Fig. 13, the current output of the hydro  
generator in Fig. 14, the current output of the DFIG in Fig. 15, and the current through Bus 3 in Fig. 16.  
Fig.13 Current exchanged with the grid in Scenario 1  
Fig.14 Current from the hydro plant to Bus 3 in Scenario 1  
Page 2092  
Fig.15 Current from the DFIG to Bus 3 in Scenario 1  
Fig.16 Current through Bus 3 in Scenario 1  
It can be observed that the current exchanged with the grid and the current through Bus 3 have similar waveforms,  
differing only in magnitude due to the voltage level difference and the power losses on transmission line L1.  
Scenario 2: Single-phase-to-ground fault lasting 0.1 s  
The simulation results for Scenario 2 (single-phase-to-ground fault of 0.1 s) regarding the grid current, hydro  
generator current, DFIG current, and Bus 3 current are presented in Fig. 1720.  
Fig.17 Current exchanged with the grid in Scenario 2  
Fig.18 Current from the hydro generator in Scenario 2  
Fig.19 Current from the DFIG in Scenario 2  
Page 2093  
Fig.20 Current through Bus 3 in Scenario 2  
Scenario 3: Three-phase-to-ground fault lasting 0.1 s  
Fig. 2124 present the simulation results of Scenario 4, i.e., a three-phase-to-ground fault of 0.1 s, including the  
grid current, hydro generator current, DFIG current, and the current through Bus 3.  
Fig.21 Current exchanged with the grid in Scenario 3  
Fig.22 Current from the hydro generator in Scenario 3  
Fig.23 Current from the DFIG in Scenario 3  
Fig.24 Current through Bus 3 in Scenario 3  
The simulation results for Scenarios 2 and 3 show that the fault currents from the power source, hydro generator,  
and DFIG surge at t=6 s. The hydro generator exhibits a different transient response compared with the power  
Page 2094  
source and the DFIG, due to the influence of the excitation system. Since the fault is cleared at t=6.1, the protection  
of the hydro generator and DFIG is not triggered. These results accurately reflect the transient behavior of system  
components under temporary faults.  
Scenario 4: Single-phase-to-ground fault lasting 1 s  
Fig. 2528 present the simulation results of Scenario 4, i.e., a single-phase-to-ground fault of 0.9 s, including the  
grid current, hydro generator current, DFIG current, and the current through Bus 3.  
Fig.25 Current exchanged with the grid in Scenario 4  
Fig.26 Current from the hydro generator in Scenario 4  
Fig.27 Current from the DFIG in Scenario 4  
Fig.28 Current through Bus 3 in Scenario 4  
Scenario 5: Three-phase-to-ground fault lasting 1 s  
Fig. 2932 present the simulation results of Scenario 5, i.e., a three-phase-to-ground fault of 0.9 s, including the  
grid current, hydro generator current, DFIG current, and the current through Bus 3.  
Page 2095  
Fig.29 Current exchanged with the grid in Scenario 5  
Fig.30 Current from the hydro generator in Scenario 5  
Fig.31 Current from the DFIG in Scenario 5  
Fig.32 Current through Bus 3 in Scenario 5  
The results for Scenarios 4 and 5 indicate that the short-circuit currents from the power source, hydro generator,  
and DFIG surge at t=6 s and last until t=6.9 s. Both the hydro generator and the DFIG cease power generation  
after the fault due to the governor triggering the disconnection of circuit breakers from the system. Although the  
fault is cleared at t=6.9 s, both generators remain disconnected, so the power source supplies the load. This reflects  
the system behavior under sustained faults, including both single-phase and three-phase short-circuits.  
CONCLUSIONS  
The main contribution of this paper is the successful simulation and analysis of short-circuit currents in a power  
system that simultaneously integrates a small hydro generator and a DFIG-based wind plant. The system  
configuration and the DFIG control structure are detailed, including the use of power electronic converters for  
controlling rotor-side and grid-side power flows. Several fault scenarios were established, including faults at buses  
Page 2096  
connected to the DFIG and hydro generator, to evaluate the transient current responses and the ability of different  
generators to support the system.  
The results show that the fault current contribution from the hydro generator is large in the initial stage and decays  
according to the subtransient, transient, and steady-state time constants, consistent with synchronous generator  
characteristics. In contrast, the fault current from the DFIG is limited by the converter and crowbar protection  
mechanism, with its behavior depending on the control strategy and LVRT mode. This highlights the distinct  
contributions of the two generation types to short-circuit currents.  
Such analysis and comparison accurately reflect the distribution of power, current magnitude, and phase at system  
nodes, thereby providing a comprehensive view of system responses under fault conditions. These findings offer  
system operators a technical basis for evaluating stability margins and for determining generation dispatch or  
load-shedding strategies under severe contingencies.  
The contributions of this study can be extended in future work by considering more complex fault scenarios, such  
as faults within the DFIG itself, multiple simultaneous faults in weak grids, or coordination among multiple  
distributed generators. Such analyses will further enhance the reliability and stability of modern power systems  
with high penetration of renewable energy sources.  
ACKNOWLEDGMENTS  
This study is completely supported by Thai Nguyen University of Technology, Thai Nguyen University, Viet  
Nam.  
REFERENCES  
1. J. Yin, “Improved Short-Circuit Current Calculation of Doubly Fed Wind Turbines With Uninterrupted  
Excitation,” Frontiers in Energy Research, vol. 9, 2021. Frontiers  
2. F. Xiao, Y. Xia, K. Zhang, Z. Zhang, and X. Yin, “Short-circuit model of the DFIG considering  
coordinated control strategy of grid- and rotor-side converters,” Electric Power Systems Research, vol.  
202, 2022. ScienceDirect  
3. A. Arastou, “Parameter identification of small distributed hydro generators under sudden short circuit  
test,” IET Generation, Transmission & Distribution, vol. 16, issue not., 2022. IET Research Journals  
4. D. Brankovic and F. Schuerhuber, “Short-circuit current of a hydropower plant with consideration of  
constant switching and fault arc voltages,” IET Generation, Transmission & Distribution, 2024. IET  
5. J. Yin, “A New Short-Circuit Current Calculation and Fault Analysis Model for Doubly Fed Induction  
Generator,” PMC, 2023. PMC  
6. R. He, “Calculation method of external fault short-circuit current for variable-speed pumped storage  
units,” Frontiers in Energy Research, 2023. Frontiers  
7. A. Gozdowiak and M. Antal, “Inter-Turn Short Circuits in Stator Winding of Permanent Magnet  
Synchronous Generator Dedicated for Small Hydroelectric Power Plants,” Energies, vol. 18, no. 14,  
2025. MDPI  
8. J. Yin, “Influence of Reactive Power Support Control Strategy on Short-Circuit Current Calculation and  
Fault Analysis Method of DFIG,” Frontiers in Energy Research, 2021. ADS  
9. J. Yin et al., “Short Circuit Current Analysis Of DFIG-Type Wind Generator with Crowbar Action,”  
(conference / preprint) 202x. Bohrium  
10. C. Geiger et al., “Power Plant Transients including Hydraulic Short Circuit in Hydro Power Plant,”  
Energies, 2023. MDPI  
11. Richard  
Gagnon,  
Bernard  
Saulnier,  
Alain  
Forcione  
(Hydro-Quebec),  
Page 2097