INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3885
www.rsisinternational.org
Assessment of Load Characteristics in Short-Circuit Studies of
Distribution Substations
Nguyen Thi Thanh Thuy*
Electrical Faculty, Thai Nguyen University of Technology, Thai Nguyen, Viet Nam
*Corresponding Author: thuyhtd@tnut.edu.vn
DOI: https://dx.doi.org/10.51244/IJRSI.2025.1210000335
Received: 08 November 2025; Accepted: 15 November 2025; Published: 22 November 2025
ABSTRACT
This paper evaluates the influence of electrical loads on the distribution of currents under both normal and fault
operating conditions in distribution substations. Static and dynamic loads are modeled using equivalent
impedance components, where dynamic loads are represented by the Conventional Load Model, Exponential
Load Model, Polynomial Load Model, and Comprehensive Load Model. The Newton-Raphson method is
applied for power flow analysis to determine current distribution under normal operating states. In addition, the
IEC short-circuit calculation method is adopted to analyze fault current distribution in the entire system under
short-circuit conditions. A five-bus test system, in which the load can switch between static and composite
(static + dynamic), is proposed to investigate current distribution under different operating conditions.
Simulations are performed in ETAP for both normal and fault modes, considering static loads and composite
loads. The results highlight current distribution across the system, clarifying the ability of dynamic loads to
contribute to fault currents during short-circuit conditions, unlike static loads. The contributions of this study
provide insights for designers and operators in understanding how electrical load characteristics affect the
performance of protection devices in distribution substations.
Index Terms: Composed Load, Electrical Load Model, Static Load, Motor Load, Newton-Rahpson method,
Short-Circuit Calculation.
INTRODUCTION
Electrical loads in distribution substations are diverse and vary depending on multiple factors, including
technological advancements and consumption patterns. Each type of load possesses unique characteristics that
influence the calculation of aggregated loads and the selection of protective devices. The contribution of loads
to the current in different operating modes of the substation depends on both load types and operating states,
and thus requires detailed evaluation.
Electrical loads in distribution substations are highly diverse and evolve in line with the development of
production technologies as well as the consumption characteristics of different categories of equipment [1], [2].
Each type of load exhibits distinct characteristics that directly affect the calculation of aggregated loads and the
selection of appropriate protective devices [3]. In power systems, loads are commonly categorized into Static
Loads (SL) and Dynamic Loads (DL). Static loads include electrical equipment without rotating elements, such
as lighting systems, electronic devices, and resistive appliances [4]. In contrast, dynamic loads are devices
driven by electric motors, such as pumps, fans, or compressors, which, due to their mechanical inertia, can
continue to supply energy for a short duration even after being disconnected from the power source [5], [6].
This characteristic allows dynamic loads to act as potential sources contributing to fault currents and thus must
be taken into account in short-circuit analysis and protection system design [7][9].
In practical operation, loads in distribution substations often exist as Composed Loads (CL), i.e., a combination
of static and dynamic loads. The proportion between these two components determines the electrical
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3886
www.rsisinternational.org
characteristics at each bus, thereby affecting the selection of conductors, switching devices, and protection
strategies [10], [11]. Recent studies have also indicated that the development of distributed generation and
renewable energy sources has increased the demand for improved load models to more accurately reflect the
operational behavior of modern distribution networks [12][14]. Furthermore, experimental results
demonstrate the need to consider the ZIP characteristics (ZImpedance, ICurrent, PPower) when modeling
residential, commercial, and industrial loads [15].
Under normal operating conditions, loads determine the power and current levels that equipment must
withstand over long durations, thereby influencing the lifetime and reliability of the system [16]. In fault
conditionsparticularly single-line-to-ground and three-phase short circuitsthe current often far exceeds the
rated value and may cause severe damage to conductive elements if not properly protected [2], [7]. Moreover,
recent research shows that the participation of dynamic loads and renewable energy sources can significantly
alter fault current distribution, necessitating adjustments in short-circuit analysis and relay protection design
[8], [9], [12], [17], [18]. This is critical because the contribution of fault currents from dynamic loads can
directly affect the breaking capability of circuit breakers, the operating conditions of relays, and the thermal
endurance of conductors in distribution substations [13], [14], [19][21].
Based on the above analysis, this paper focuses on evaluating the impact of loads on current distribution in
distribution substations. Section II presents the modeling methods of electrical loads, including static and
dynamic loads. Section III introduces analytical methods for network operation under both normal and short-
circuit conditions. Section IV presents simulation results, highlighting the differences between Static Loads
(SL) and Composed Loads (CL). Finally, Section V concludes with key findings derived from this study.
LOAD MODELING
A. Static Load Model
A static load is defined by its active power (P), reactive power (Q), apparent power (S), and power factor
(cosφ). The mathematical relationships of these parameters are expressed as follows [4]:
22
S P Q
(1)
cos
P
S
(2)
where: P, Q, S are active power, reactive power, apparent power; cos is power factor.
Static loads typically consist of devices with constant or slowly varying currents, such as lighting equipment,
electric heaters, or electronic devices. Their power consumption is nearly independent of sudden voltage
changes, and thus, they rarely pose issues related to transient behavior or stability in the system.
B. Dynamic Load Models
Dynamic loads, particularly induction motors, represent the majority of industrial and commercial loads. Their
operating characteristics differ significantly from static loads because they involve rotating mechanical
components and inertia [5], [6]. When subject to voltage disturbances or during start-up, these loads exhibit
non-linear behavior that strongly affects system stability. To analyze them accurately, different mathematical
models are employed:
1) Conventional Load Model
The conventional representation assumes that the dynamic load can be modeled as a constant impedance at the
fundamental frequency. This approach is widely applied in short-circuit studies because it allows motors to be
represented as equivalent sources contributing to fault currents [4], [25].
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3887
www.rsisinternational.org
Exponential Load Model [7-9], [25]:
0
1
a
pf
P PU K f
(3)
0
1
b
qf
Q Q U K f
(4)
where:
P
0
, Q
0
: reference active and reactive power at nominal voltage U
0
;
P, Q are active power, reactive power at voltage U and frequency difference f;
;
f is current frequency of the system;
f
0
is norminal frequency of the system;
The parameters a and b represent the exponential indices that characterize the load behavior. Specifically, a
value of 0 corresponds to a Constant Power load, a value of 1 corresponds to a Constant Current load, and a
value of 2 corresponds to a Constant Impedance load. These indices are widely used in load modeling to
capture the nonlinear dependence of power consumption on bus voltage;
K
pf
=(0÷3) is the frequency-dependence coefficient of the active power component with respect to frequency
deviation;
K
qf
=(-2÷0) is the frequency-dependence coefficient of the reactive power component with respect to frequency
deviation;
Polynomial Load Model [25]:
2
0 1 2 3
1
pf
P P pU p U p K f
(5)
2
0 1 2 3
1
qf
Q Q qU q U q K f
(6)
where: p
1
, q
1
, p
2
, q
2
, p
3
, q
3
denote the power components corresponding to Constant Impedance, Constant
Current, and Constant Power characteristics, respectively. Each portion of the load is defined by these
constants.
Comprehensive Load Model:
The Comprehensive model of the Lumped Load uses the following equations to determine the real and reactive
power components of the load [10], [11], [25]:
0 EX 1 EX 2POLY P P
P P P P P
(7)
where:
2
1 2 3POLY
P pU p U p
1
EX 1 4 1
1
a
P pf
P p U K f
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3888
www.rsisinternational.org
2
EX 2 5 2
1
a
P pf
P p U K f
The formulation of the reactive load component follows an analogous structure, with reactive power
compensation modeled explicitly. The comprehensive load model integrates both polynomial and exponential
terms, parameterized by the constants p
1
, q
1
, p
2
, q
2
, p
3
, q
3
, p
4
, q
4
, p
5
, q
5
. These parameters describe the
contributions of constant impedance, constant current, constant power, and exponential elements within the
load.
The coefficients K
pf1
, K
pf2
correspond to the active power equations, typically varying in the range of 0 to 3.0.
Similarly, the coefficients K
qf1
, K
qf2
pertain to the reactive power equations, with typical values ranging from
2.0 to 0.
In addition, short-circuit contribution levels are specified separately, in accordance with the IEC methodology,
and are categorized as outlined in Table [2], [7], [25]
TABLE I. SHORT-CIRCUIT CONTRIBUTION
Short-Circuit Contribution
HP
Speed
High
Large
High RPM
Medium
Medium
Intermittent RPM
Low
Small
Low RPM
The lumped motor model includes parameters for grounding configuration, connection type, and rating. The
grounding connection can be specified by selecting among the available options, with Wye and Delta being the
supported types. The motor’s short-circuit reactance-to-resistance ratio X
sc
/R
a
, commonly referred to as the X/R
ratio, is also defined; if the Typical option is chosen, a standard representative value is automatically applied.
In addition, the transient time constant T'
d
, expressed in seconds, is considered, which is particularly relevant
for calculations performed under the IEC 61363 methodology
'
"
2
d
r
X
T
fR
(8)
where: R
r
is rotor resistance.
METHOD FOR POWER ANALYSIS UNDER NORMAL OPERATING CONDITIONS
AND SHORT-CIRCUIT SCENARIOS
A. Power analysis under normal operating conditions
Mathematical model of medium voltage transmission lines is described in Fig. 1 [22-25].
Bus i Bus j
z
ij
= R
ij
+jX
ij
Fig. 1 Mathematical model of cable in low voltage systems
Where: R
ij
() is resistance and X
ij
() is reactance of the transmission line connecting bus i and bus j.
Mathematical model of two-winding transformer is described in Fig. 2.
Bus i
Bus j
a. Power transformer
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3889
www.rsisinternational.org
Bus i
Bus j
z
T
= R
T
+jX
T
K
ij
b. Equivalent circuit
Fig. 2 Mathematical model of two-winding transformer
Where: R
T
() is resistance and X
T
() is reactance of the transformer; K
ij
is voltage ratio between bus i and
bus j of ideal transformer (without power loss). In Fig. 2b, voltage value of bus i is higher than voltage value of
bus j, so bus i is called HV bus and bus j is called LV bus.
A general distribution system include (N+1) buses, where N buses are normal buses and a bus is ground. Any
branch in the system can be classified to the standard line or transformer branch. These branches can be
defined by a general standard branch as depicted in Fig. 3 [22-25].
Bus i
Bus j
z
ij
K
ij
J
.
U
i
.
U
j
.
U
i'
.
i'
I
ij
.
.
a. Bus i connecting to the ideal transformer directly
Bus i
Bus j
K
ij
J
.
U
i
.
U
j
.
U
j'
.
j'
I
ij
.
z
ij
.
b. Bus i connecting to the ideal transformer indirectly through an impedance
Fig. 3 Diagram of general standard branch
In Fig. 3a and Fig. 3b, the current source
i
J
(from generations) is injects to bus i. If the branch describes a
transformer, voltage ratio can be calculated forward to bus i that is
'
'
i
ij
i
U
K
U
. If the branch describes a
transmission line, voltage ratio is
1
ij
K
.
Applying Kirchhoff 1, current balancing equation at bus i can be determined by (9) [7].:
0
N
ij i
j
ji
IJ
(9)
Using I’
ij
, equation (1) can be converted to equation (10):
'
0
N
ij ij i
j
ji
K I J
(10)
Using Ohm's law for i'j branch, equation (3) can be converted to equation (11) [7]:
0
N
ii k ij j i
j
ji
Y U Y U J

(11)
where:
ii
Y
is individual admittance of bus i and
ij
Y
is interactive admittance of branch ij.
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3890
www.rsisinternational.org
ii
Y
,
ij
Y
can be determined by equation (12) and (13):
2
0
N
ij
ii
j
ij
ji
K
Y
Z



(12)
ij
ij
ij
K
Y
Z

(13)
Working the same with Fig. 7b,
ii
Y
can be defined by equation (14):
0
1
N
ii
j
ij
ji
Y
Z
(14)
In general case study, bus i can be connected to m buses directly through ideal transformers and k buses
indirectly through ideal transformers.
ii
Y
can be determined by equation (15) [22-25]:
2
00
1
km
ij
ii
jj
ij ij
j i j i
K
Y
ZZ



(15)
Current balancing equations for whole system can be described in system of equations (16).
11 1 12 2 1 1
21 1 22 2 2 2
1 1 2 2
...
...
.............................................
...
NN
NN
N N NN N N
Y U Y U Y U J
Y U Y U Y U J
Y U Y U Y U J
(16)
From system of equations (16), matrix admittance can be derived as (17):
11 12 1
21 22 2
12
...
...
... ... ... ...
...
N
N
N N NN
Y Y Y
Y Y Y
Y
Y Y Y






(17)
Almost buses in distribution systems are PQ buses (load buses). Capacitors can be implemented at these buses
and considered as reactive generators. In these systems, Newton-Raphson method is often used to determine
power flows and voltage buses.
To determine operating parameters for N-bus grid by using Newton-Raphson method, system of power
balancing equations at bus i can be defined by (18) and (19) [7]:
2
1
cos cos( )
N
i ii ii i j ij i j ij Li i
j
ji
U y U U y P P
( 8)
2
1
sin sin( ) ( )
N
i ii ii i i ij i j ij Li Ci i
j
ji
U y UU y Q Q Q
( 9)
where:
1, ; ;
i i i ij ij ij
i N U U Y y

.
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3891
www.rsisinternational.org
P
Li
and Q
Li
are active and reactive load power at the bus i; Q
Ci
are active and reactive power of the capacitor
bank at the bus i.
From solutions at the k
th
step including
()k
i
and
()k
i
U
, values of
()k
i
P
and
()k
i
Q
can be calculated. Moreover,
values of
()k
i
and
()k
i
U
at the k
th
step can be calculated by using reversed Jacobian matrix as described in
equation (20):
( ) ( )
1
( ) ( )
kk
ii
kk
ii
P
J
UQ


(20)
where: J is Jacobian matrix.
Jacobian matrix at the i
th
step:
12
34
JJ
J
JJ



Solutions at the next step can be determined by equation (14) [20-21]:
( 1) ( ) ( )
( 1) ( ) ( )
k k k
i i i
k k k
i i i
U U U

(21)
This process will be stopped if both values of P
i
and Q
i
are smaller than allowable value
[7-9]. Fig. 4
describes the Newton-Raphson method to analyze a distribution system.
Start
Enter initial parameters: rated voltage; transmission lines;
transformers; electric loads at buses; bus types; acceptable
deviation of caculation; active and reactive power of generations
Calculate impedance matric (Y)
P
i
(k)
< and
Q
i
(k)
<
Y
N
Calculate Jacobian and
reservered Jacobian matrices
Assign intial values of U
i
(0) and
i
(0), i=(N)
Calculate P
i
(k)
and Q
i
(k)
Calculate U
i
(k)
and 
i
(k)
Power-flow
analysis results
Stop
k:=k+1
Fig. 4. Newton-Raphson algorithm to analyze whole grid
The NewtonRaphson method is characterized by quadratic convergence, enabling significantly faster
convergence compared to alternative load flow techniques. Its convergence process is guided by well-defined
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3892
www.rsisinternational.org
criteria that control the permissible mismatches in real and reactive power at each bus, thereby allowing direct
specification of the desired solution accuracy. In practical applications, the convergence tolerance is typically
set to 0.001 MW for active power and 0.001 MVAr for reactive power.
Despite its efficiency, the method is sensitive to the choice of initial bus voltage values. To enhance numerical
stability and reliability, careful initialization is recommended. In ETAP, several GaussSeidel iterations are
performed prior to executing the NewtonRaphson load flow, ensuring a consistent and well-conditioned set of
initial bus voltages.
B. Method for power analysis under fault conditions in accordance with IEC standard
IEC 60909 and related standards categorize short-circuit currents based on their magnitudes (maximum and
minimum) as well as their distance from the generator (near and far). Maximum short-circuit currents are used
to determine equipment rating requirements, while minimum short-circuit currents are critical for setting
protective devices. The classification into near-to-generator and far-from-generator faults dictates whether the
decay of the AC component should be explicitly considered in the calculation.
The three-phase short-circuit current (I”
k
) is evaluated using the following expression [2225]:
"
(1)
3
n
k
cU
I
Z
(22)
Two-phase short-circuit current (I”
k2
) is calculated using the following formula:
""
2
(1) (2) (1)
3
2
2
nn
kk
cU cU
II
Z Z Z
(23)
Two-phase-to-ground short-circuit current (I”
kE2E
) is calculated using the following formula [22-25]:
2
10
3
2

( ) ( )
dm
kE E
cU
I
ZZ
(24)
Single-phase-to-ground short-circuit current (I”
k1
) is calculated using the following formula [22-25]:
"
1
(1) (0)
3
2
n
k
cU
I
ZZ
(25)
where: Z
k
is the equivalent impedance at the fault location; U
n
is the normial grid voltage; Z
(1)
, Z
(2)
Z
(0)
are
the positive-sequence, negative-sequence, and zero-sequence impedances, respectively, from the source to the
fault location.
Voltage factor c: This is the factor used to adjust the value of the equivalent voltage source for minimum and
maximum current calculations according to the following table.
TABLE II. VOLTAGE FACTOR (±5% VOLTAGE TOLERANCE)
Nominal Voltage U
n
For Maximum Short-Circuit
Current Calculation (c
max
)
For Minimum Short-Circuit
Calculation (c
min
)
Others < 1000 V
1.05
0.95
Medium voltage: > 1 kV to 230 kV
1.10
1.00
High voltage: > 230 kV
1.10
1.00
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3893
www.rsisinternational.org
TABLE III. VOLTAGE FACTOR (±10% VOLTAGE TOLERANCE)
Nominal Voltage U
n
For Maximum Short-Circuit
Current Calculation (c
max
)
For Minimum Short-Circuit
Calculation (c
min
)
Others < 1000 V
1.10
0.90
Medium voltage: > 1 kV to 230 kV
1.10
1.00
High voltage: > 230 kV
1.10
1.00
SIMULATION
A. Simulation parameters
Consider the power system network of a distribution substation with five buses, as illustrated in Fig. 5,
hereafter referred to as the E-5bus system.
~
Source
2 3
4
Load3
Load5
5
Load4
Load2
T1
1
Fig. 5. Diagram of E-5bus
Parameters of transmission lines in Table IV, power source in Table V, transformers in Table VI, electric load
at bused using exponential model in Table VII.
TABLE IV. PARAMETERS OF TRANSMISSION LINES
Name
Sectional area of a conductor (mm
2
)
Insulation
Length (m)
Number of conductors/phase
Bus B2 - Bus B3
400
XLPE
100
1
Bus B3 - Bus B4
240
XLPE
60
1
Bus B3 - Bus B5
95
XLPE
50
1
TABLE V. PARAMETERS OF SOURCE
Type
Parameters
Power system
Rated voltage: 22 kV; Short-circuit power: 300 MVA; Reactance/Resistance: 10
TABLE VI. TRANSFORMERS
Location
Parameters
T1
Voltage ratio: 22/0.4 kV; Rated power: 4 MVA; Impedance: Z=8.35%; Reactance/Resistance=13
TABLE VII. PARAMETERS OF ELECTRIC LOAD AT BUSES
Name
Static load and conventional load
Composed load (Exponential model)
Power (kVA)
Power factor
Ratio
P
0
(kW)
Q
0
(kVAr)
a
b
K
pf
K
qf
Load B2
250
0.9
50%
230
100
1
2
0.1
0.1
Load B3
180
0.9
50%
162
80
2
1
0.1
0.1
Load B4
400
0.9
50%
230
100
1
1
0.2
0.2
Load B5
250
0.9
50%
360
175
3
1
0.15
0.1
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3894
www.rsisinternational.org
B. Simulation results
The NewtonRaphson method and ETAP software are employed to simulate the E-5bus network using the
parameters provided in the above table. The simulation results for the operating condition with all static loads
are presented in Fig. 6, while the aggregated load modeled with the conventional approach is illustrated in Fig.
7. The results of three-phase and single-phase short-circuit faults at location F1 are shown in Fig. 8 for the
static load case and in Fig. 9 for the dynamic load case.
Fig. 6 Current distribution under normal operating conditions when all loads are static, based on the
Conventional Model
Fig. 7 Current distribution under normal operating conditions with mixed loads, based on the Conventional
Model
a. Three-phase short circuit
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3895
www.rsisinternational.org
b. Single-phase-to-ground short circuit
Fig. 8 Current distribution under fault condition at bus B3 when all loads are static, based on the Conventional
Model.
The simulation results of three-phase and single-phase short-circuit faults at fault location F1 are presented in
Fig. 9.
a. Three-phase short circuit
b. Single-phase-to-ground short circuit
Fig. 9 Current distribution under fault condition at bus B3 with mixed loads, based on the Conventional Model
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3896
www.rsisinternational.org
The simulation results of three-phase and single-phase short-circuit faults at fault location F2 are shown in Fig.
10 for static loads and Fig. 11 for dynamic loads.
a. Three-phase short circuit
b. Single-phase-to-ground short circuit
Fig. 10 Current distribution under fault condition at bus B4 when all loads are static, based on the Conventional
Model
a. Three-phase short circuit
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3897
www.rsisinternational.org
b. Single-phase-to-ground short circuit
Fig. 11 Current distribution under fault condition at bus B4 with mixed loads, based on the Conventional
Model
From the above simulation results, the current distribution across the entire network under normal operating
conditions, for both static and aggregated loads, is illustrated in Fig. 12.
2 3
4
Load3
Load5
5
Load4
Load2
I
23
I
34
I
35
S
load2
S
load3
S
load5
~
Source
T1
1
Fig. 12 Current distribution under normal operating conditions, based on the Conventional Model
For a short-circuit fault at F1, the current distribution in the network is shown in Fig. 13a for static loads and in
Fig. 13b for aggregated loads.
2
3
4
Load3
Load5
5
Load4
Load2
I
F1
F1
~
Source
T1
1
a. Loads including all static components
2
3
4
Load3
Load5
5
Load4
Load2
I
F1
I
F23
I
F24
~
Source
T1
1
F1
b. Load including dynamic components
Fig. 13 Current distribution in the substation under a fault at F1, based on the Conventional Model
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3898
www.rsisinternational.org
For a short-circuit fault at F2, the current distribution in the network is shown in Fig. 14a for static loads and in
Fig. 14b for aggregated loads.
2 3
4
Load3
Load5
5
Load4
Load2
I
F2
F2
I
23
~
Source
T1
1
a. Loads including all static components
2 3
4
Load3
Load5
5
Load4
Load2
I
F34
F2
I
F23
~
Source
T1
1
I
F35
b. Load including dynamic components
Fig. 14 Current distribution in the substation under a fault at F2, based on the Conventional Model
The simulation results of current distribution considering the Exponential Load Model under a short-circuit
fault at F1 are illustrated in Fig. 15.
a. Normal operating conditions
b. Three-phase short circuit
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3899
www.rsisinternational.org
c. Single-phase-to-ground short circuit
Fig. 5 Current distribution in the substation under a fault at F1 based on the Exponential Load Model
The above figures demonstrate that the overall current distribution in the network remains unchanged
regardless of whether the load is static or dynamic. In the case of static loads under fault conditions, the load
does not contribute any current to the fault location, irrespective of the fault position within the network. By
contrast, when dynamic loads are considered under the Conventional Model, the loads contribute current to the
fault location, regardless of whether the fault occurs at the sending or receiving end of the feeder. The
magnitude of the fault current contribution depends on the proportion of motor load: the larger the motor share,
the greater the contribution. Under fault conditions with motor participation, the motors behave as internal
sources, injecting fault current into the fault point. However, under the Exponential Load Model, dynamic
loads do not contribute any current to the fault location, and the other load models yield similar results.
CONCLUSIONS
The contribution of this paper is the assessment of the impact of static and dynamic loads on the distribution of
short-circuit currents in distribution substations. These load types are modeled through various approaches,
including the Static Load Model, Conventional Load Model, Exponential Load Model, Polynomial Load
Model, and Comprehensive Load Model. The NewtonRaphson method is applied for load flow analysis under
normal operating conditions, while the IEC short-circuit calculation methodology is employed to determine
operating parameters under fault conditions. All system components are modeled and analyzed in ETAP
software.
The simulation results indicate that the current distribution and bus voltage parameters under normal operating
conditions are not affected by the type of load. This implies that the steady-state operation of the substation,
which corresponds to its long-term performance, remains independent of load characteristics. Under fault
conditions, however, motor loads influence fault current contributions when represented by the Conventional
Load Model, in which the load behaves as an additional current source at the fault location. In contrast, when
the Exponential, Polynomial, or Comprehensive Load Models are used, the load does not contribute to fault
current under any fault scenario. In such cases, dynamic loads behave equivalently to static loads with respect
to short-circuit current contribution.
The findings of this study can be applied to the design and operation of distribution substations. Designers and
operators must carefully select appropriate load models and account for the extent of load contribution to short-
circuit currents in order to properly coordinate protection systems and evaluate fault current magnitudes. Future
work will further investigate the design and operation of protective relaying systems, explicitly considering the
contribution of load current during fault conditions.
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3900
www.rsisinternational.org
ACKNOWLEDGMENTS
This study is completely supported by Thai Nguyen University of Technology, Thai Nguyen University, Viet
Nam.
REFERENCES
1. S. Subedi, H. Zhou, H. Karki, and B. Poudel, “Aggregate data-driven dynamic modeling of active
distribution networks with DERs for voltage stability studies,” IET Renewable Power Generation, vol.
18, no. 6, pp. 678689, Jun. 2024.
2. Y. Liu, Z. Guo, and X. Zhang, “Real-time short-circuit current calculation in electrical distribution
systems considering the uncertainty of renewable resources and electricity loads,” Applied Sciences,
vol. 14, no. 23, p. 11001, 2024.
3. S. Hill, A. Hughes, and P. Clarkson, Improved load modelling for emerging distribution system
assessments,” CIRED Open Access Proceedings Journal, vol. 2021, no. 1, pp. 13011305, 2021.
4. D. Del Giudice, F. Viola, and M. Rinaldi, “Definition of static and dynamic load models for grid studies
of electric vehicles connected to fast charging stations,” arXiv preprint arXiv:2302.03943, 2023.
5. D. Madjovski, I. Dumancic, and L. Petkovska, “Dynamic modeling of distribution power systems with
renewable generation for stability analysis,” Energies, vol. 17, no. 20, p. 5178, Oct. 2024.
6. Bokhari, R. Billinton, and W. Xu, “Experimental determination of the ZIP coefficients for modern
residential, commercial, and industrial loads,” IEEE Trans. Power Delivery, vol. 29, no. 3, pp. 1447
1455, Jun. 2014.
7. J. Li, H. Zhao, and Y. Wei, “A practical short-circuit current calculation method for renewable energy
plants based on single-machine multiplication,” Electricity, vol. 6, no. 1, p. 7, 2025.
8. Niersbach, A. Ghourabi, and A. Hanson, “Advanced modelling of inverter-based generators for short-
circuit current calculations based on IEC 60909-0:2016,” in Proc. CIRED Conf., 2019.
9. M. S. Nizam, R. Islam, and M. T. Rahman, “Comparison of peak short-circuit current between
traditional and renewable energy sources,” in Proc. IET Conf. on Renewable Power Generation, 2023.
10. T. Riedlinger, P. Wintzek, and M. Zdrallek, “Development of a new modelling concept for power flow
calculations across voltage levels,” Electricity, vol. 5, no. 2, p. 10, 2024.
11. O. D. Montoya, A. Rajagopalan, and F. Moya, “Optimal capacitor placement and its effect on
distribution network operation,” Mathematics, vol. 10, no. 16, p. 1600, 2022.
12. H. Jayasinghe, K. Gunawardane, and R. Nicholson, “Applications of electrical load modelling in digital
twins of power systems,” Energies, vol. 18, no. 4, p. 775, Feb. 2025.
13. T. Huang, L. Li, and K. Zhang, “Optimal operation of renewable energy bases considering short-circuit
ratio and transient overvoltage constraints,” Energies, vol. 18, no. 5, p. 1256, Mar. 2025.
14. R. Zhang, K. Qu, and C. Zhao, Robust distribution network reconfiguration using mapping-based
column-and-constraint generation,” arXiv preprint arXiv:2505.24677, 2025.
15. Abdelaziz, A. El-Dib, and R. El-Shatshat, Distribution load flow methods for modern distribution
systems: A review,” Electric Power Systems Research, vol. 163, pp. 616627, Oct. 2018.
16. H. Saadat and D. Manz, Newton-Raphson power flow for distribution systems with distributed
generation,” Int. J. of Electrical Power & Energy Systems, vol. 78, pp. 802813, 2016.
17. Y. Sun, J. Zhang, and L. Wang, “Probabilistic load flow calculation of AC/DC hybrid system based on
cumulant method,” arXiv preprint arXiv:2201.12571, 2022.
18. M. Yang, R. Xie, and Y. Zhang, “Robust microgrid dispatch with real-time energy sharing and
endogenous uncertainty,arXiv preprint arXiv:2403.15219, 2024.
19. L. Yang, H. Yang, and X. Cao, “Distributionally robust frequency-constrained microgrid scheduling
towards seamless islanding,” arXiv preprint arXiv:2401.03381, 2024.
20. K. Hoseinzadeh and F. Blaabjerg, “A novel control technique for on-load tap changer to enlarge
reactive power capability of wind power plants,” IET Generation, Transmission & Distribution, vol. 16,
pp. 29282938, 2022.
INTERNATIONAL JOURNAL OF RESEARCH AND SCIENTIFIC INNOVATION (IJRSI)
ISSN No. 2321-2705 | DOI: 10.51244/IJRSI |Volume XII Issue X October 2025
Page 3901
www.rsisinternational.org
21. K. Yoon, J. Shin, and T. Nam, Operation method of on-load tap changer on main transformer
considering reverse power flow in distribution system connected with high penetration of photovoltaic
system,” Energies, vol. 15, no. 17, p. 6473, 2022.
22. H. Luo, J. Wu, and Z. Wang, “A dynamic reconfiguration model and method for load balancing in the
snow-shaped distribution network,Frontiers in Energy Research, vol. 12, p. 1361559, 2024.
23. E. Zarate-Perez, J. Silva, and F. Lopez, “Assessment and optimization of residential microgrid based on
PV, wind & BESS using GA and ACO,Processes, vol. 13, no. 3, p. 740, 2025.
24. S. Phommixay, M. Doumbia, and D. Lupien St-Pierre, “Review on the cost optimization of microgrids
via particle swarm optimization,” Energy Systems, vol. 11, pp. 445468, 2020.
25. ETAP, ETAP Power System Analysis User Guide Load Flow and Short-Circuit Modules, Operation
Technology Inc., 2020.