Fault Analysis Detection and Protection of Transmission Line By PSCAD

Authors

Anil Kumar Rajak

Takshakshila Institute of Engineering and Technologhy, Jabalpur, Madhya Pradesh (India)

Prof. Preeti Rajput

Takshakshila Institute of Engineering and Technologhy, Jabalpur, Madhya Pradesh (India)

Milan Choubey

Takshakshila Institute of Engineering and Technologhy, Jabalpur, Madhya Pradesh (India)

Article Information

DOI: 10.51244/IJRSI.2026.1307000232

Subject Category: Energy

Volume/Issue: 13/7 | Page No: 3206-3225

Publication Timeline

Submitted: 2026-07-26

Accepted: 2026-08-01

Published: 2026-08-08

Abstract

Protection of electrical power systems is the major issue in power industry and for the protection of these electric power systems, current distance relays are widely applied due to their inherent simplicity, excellent sensitivity on internal faults and high stability on external faults. This work represented the problems on transmission line in different type of zones. The conventional digital distance relay used for the protection of transmission lines fed from one end. Therefore, algorithm for digital distance relaying is presented for the station of errors produced by the conventional digital distance relay during a high resistance single line to ground fault or line to line fault. In this paper the algorithm is based on digital computation of impedance, which uses symmetrical components of three- phase currents and voltages measured at the local end only. The distance is divided into zone 1,zone 2 and zone 3. This paper may help to identify the fault on a transmission line and also help to improve the power factor of the system. The proposed algorithm has been tested usings software for a single line-to-ground and line-to-line fault which consider wide variations in fault resistance, fault location, power factor, and short-circuit capacity of the source, the Power Systems Computer Aided Design (PSCAD) simulation environment. A 132 kV transmission line model was developed in PSCAD, and different fault conditions including Single Line-to-Ground (LG), Line-to-Line (LL), Double Line-to-Ground (LLG), and Three-Phase (LLL) faults were simulated and analyzed. The performance of the distance relay was evaluated based on voltage, current, impedance, fault location, and relay operating time under different fault conditions. The simulation results demonstrate that the proposed protection scheme accurately detects and classifies faults, identifies the fault location, and operates effectively within the predefined protection zones (Zone-1, Zone-2, and Zone-3). Among the analyzed faults, the Line-to-Ground fault was found to be the most frequent, whereas the Three-Phase fault produced the highest fault current. The study confirms that PSCAD is an effective tool for transmission line fault analysis and relay performance evaluation, thereby improving the reliability, selectivity, and security of modern power transmission systems.

Keywords

N/A

Downloads

References

1. Farhana Ferdous, Ruma, “Zone Protection System of Transmission Line By Distance Relay using Matlab/Simulink”, International Conference on Advancement in Electrical and Electronic Engineering, 22-24 November, 2018, Gazipur, Bangladesh, 978-1-5386-8252-4/18/©2018 IEEE. [Google Scholar] [Crossref]

2. Sabyasachi Behera P. Raja and S. Moorthi, “Modelling and simulation of the impact of SVC on existing distance relay for transmission line protection”, 2015 International Conference on Condition Assessment Techniques in Electrical Systems (CATCON), 5/15/2015 IEEE. [Google Scholar] [Crossref]

3. Y. Zhong, X. N. Kang, Z. B. Jiao, “A Novel Distance Protection Algorithm for Long-Distance Transmission Lines”, 8/16/2016 IEEE. [Google Scholar] [Crossref]

4. A. Y. Abdelaziz, M. Abdel Rahman, M. S. Moussa, “Distance Protection for Multi-terminal Transmission Lines”, 2011 2nd International Conference on Electric Power and Energy Conversion Systems (EPECS), ©2011 IEEE. [Google Scholar] [Crossref]

5. Sadegh Azizi, Majid Sanaye-Pasand and Mario Paolone, “A Modified Formula for Distance Relaying of Tapped Transmission Lines With Grounded Neutrals”, IEEE Transactions on Power Delivery, Vol. 34, No. 2, April 2019. [Google Scholar] [Crossref]

6. Jong-Man Cho, Chang-Ho Jung, Jin-O Kim, “Adaptive Setting of Digital Relay for Transmission Line Protection”, PowerCon 2000 International Conference on Power System Technology, Proceedings, 2000 IEEE. [Google Scholar] [Crossref]

7. H. Shateri and S. Jamali, “Distance Relays Ideal Tripping Characteristic in Presence of Directly Connected Load to Transmission Lines”, 978-14244-3811-2/09/©2009 IEEE. [Google Scholar] [Crossref]

8. M. M. Eissa and M. Masoud, “A Novel Digital Distance Relaying Technique for Transmission Line Protection”, IEEE Transactions on Power Delivery, Vol. 16, No. 3, July 2001. [Google Scholar] [Crossref]

9. A. Kazemi, S. Jamali and H. Shateri, “Measured Impedance by Distance Relay in Presence of SVC on Transmission Line”, 1-4244-0136-4/06 ©2006 IEEE. [Google Scholar] [Crossref]

10. A. M. Purohit, V. N. Gohokar, “Analysis of distance relay performance in protection of high voltage transmission line”, Int. Co. on C. C. and Energy S., P. ID-EE01, Jan-2016. [Google Scholar] [Crossref]

11. M. Rambabu, M. Venkatesh, J. S. V. Sivakumar and T. S. I. V. Ayya Rao, “Three zone protection by using distance relays in Simulink/MATLAB”, Int. Ref. J. Engg. and Tech. (IRJET), Vol. 02, Issue 05, Aug. 2015, pp. 810-819. [Google Scholar] [Crossref]

12. V. K. Mehta, Rohit Mehta, “Principles of Power System”, 4th Revised Edition, ISBN 81-219-2496-0. [Google Scholar] [Crossref]

13. Transmission line: An optimization technique for charging current compensation. ARPN Journal of Engineering and Applied Science, Vol. 13, No. 2, January 2018. [Google Scholar] [Crossref]

14. N. Kang and Y. Liao, “Double-Circuit Transmission-Line Fault Location with the Availability of Limited Voltage Measurements,” IEEE Transactions on Power Delivery, Vol. 27, No. 1, pp. 325-336, Apr. 2011. [Google Scholar] [Crossref]

15. A. Esmaeilian, M. Kezunovic, “An Impedance Based Fault Location Algorithm for Tapped N. Kang and Y. Liao, ‘Double-Circuit Transmission-Line Fault Location with the Availability of Limited Voltage Measurements,’” IEEE Transactions on Power Delivery, Vol. 27, No. 1, pp. 325-336, Apr. 2011. [Google Scholar] [Crossref]

16. Esmaeilian, M. Kezunovic, “An Impedance Based Fault Location Algorithm for Tapped Lines Using Local Measurements,” The 45th North American Power Symposium (NAPS), USA, Sep. 2013. [Google Scholar] [Crossref]

17. C. Y. Evrenosoglu and A. Abur, “Travelling Wave Based Fault Location for Teed Circuits,” IEEE Transactions on Power Delivery, Vol. 20, No. 2, pp. 1115-1121, Apr. 2005. [Google Scholar] [Crossref]

18. M. Korkali, H. Lev-Ari and A. Abur, “Traveling-Wave-Based Fault-Location Technique for Transmission Grids Via Wide-Area Synchronized Voltage Measurements,” IEEE Transactions on Power Delivery, Vol. 27, No. 2, pp. 1003-1011, May 2012. [Google Scholar] [Crossref]

19. A. T. Johns, R. K. Aggarwal and Z. Q. Bo, “A novel non-unit protection technique for EHV transmission systems based on fault-generated noise. Part 1. Signal measurement,” IEE Proceedings: Generation, Transmission and Distribution, Vol. 141, No. 2, pp. 133-140, 1994. [Google Scholar] [Crossref]

20. A. Abdullah, A. Esmaeilian, G. Gurrala, P. Dutta, T. Popovic, M. Kezunovic, “Test Bed for Cascading Failure Scenarios Evaluation,” IPST 2013, Vancouver, Canada, Jul. 2013. [Google Scholar] [Crossref]

21. A. Gopalakrishnan, et al., “Fault location using distributed parameter transmission line model,” IEEE Transactions on Power Delivery, Vol. 15, No. 4, pp. 1169-1174, Oct. 2000. [Google Scholar] [Crossref]

22. N. Zhang and M. Kezunovic, “A Real Time Fault Analysis Tool for Monitoring Operation of Transmission Line Protective Relay,” Electric Power Systems Research Journal, Vol. 77, No. 3-4, pp. 361-370, Mar. 2007. [Google Scholar] [Crossref]

23. J.-Z. Yang et al., “An adaptive PMU based fault detection/location technique for transmission lines. I. Theory and algorithms,” IEEE Transactions on Power Delivery, Vol. 15, No. 2, pp. 486-493, Apr. 2000. [Google Scholar] [Crossref]

24. P.-C. Chen, et al., “Locating sub-cycle faults in distribution network applying half-cycle DFT method,” IEEE PES 2014 T&D Conference and Exposition, pp. 1-5, Apr. 2014. [Google Scholar] [Crossref]