Comparative Analysis of Special Moment Bearing Frame System with Modified Structure Planning Using Double System on Bluecross Medika International Beauty Clinic Building
- Anggik Ayu Trisnawati
- I. Ketut Yasa Bagiarta
- Putu Aryastana
- 1337-1347
- Aug 19, 2025
- Civil Engineering
Comparative Analysis of Special Moment Bearing Frame System with Modified Structure Planning Using Double System on Bluecross Medika International Beauty Clinic Building
Anggik Ayu Trisnawati1, I. Ketut Yasa Bagiarta1, Putu Aryastana1,2*
1Department of Civil Engineering, Warmadewa University, Denpasar, Bali, Indonesia
2Master of Infrastructure and Environmental Engineering, Warmadewa University, Denpasar, Bali, Indonesia
*Corresponding Author
DOI: https://doi.org/10.51584/IJRIAS.2025.100700121
Received: 12 July 2025; Accepted: 18 July 2025; Published: 19 August 2025
ABSTRACT
In line with the developments that occur, many high-rise buildings are increasingly being built. An important consideration in the planning of multi-storey buildings is the earthquake force, so it is necessary to choose a good structural system in overcoming these problems. The special moment-bearing frame system is one of the structural systems that is often chosen. In addition, the moment-bearing frame system is often combined with shear walls (Double System), As shear walls enhance earthquake resistance. The purpose of this research is to compare the planning of SMRFS (Special moment resisting frame system) and Dual System structures and compare the efficiency of the behavior of these structures. The comparison of SRPMK and Dual System planning lies in the parameters used in earthquake loading, where the value of (R) = 8, (Ω0) = 3, (Cd) = 5.5 for SRPMK and (R) = 7, (Ω0) = 2.5, (Cd) = 5.5 for Dual System. The x-direction SRMPK structure is 25,463 mm and the y-direction is 22,905 mm, for the dual system the x-direction is 16,507 mm and the y-direction is 20,508 mm. The use of dual system structures is more efficient because the resulting displacement value is smaller than SRPMK. The deviation values of the two structures meet the criteria for deviation requirements, and the use of dual systems is better at accepting earthquake loads than SRPMK. By comparing the SMRFS and the dual system, we can find out the right decision in choosing the most appropriate structural system, resulting in a safe, reliable and efficient building.
Keywords: Special Moment Bearing Frame System, Double System, Earthquake Load.
INTRODUCTION
Bali is a densely populated area and one of the tourist destinations. This causes Bali to experience rapid population and economic development resulting in limited land. So that the construction of multi-storey buildings to solve the problem [1].
Bluecross Medika International Beauty Clinic is a high-rise building that has a function as a health facility and medical services and care for people in need. In the planning of high-rise building construction, there are things that must be considered, namely the earthquake force that occurs [1]. The taller the building, the more vulnerable it is to lateral forces [2], especially earthquake forces. Therefore, in earthquake-prone areas such as Indonesia, comprehensive planning of earthquake-resistant building designs is necessary [3][4][5][6].
One alternative to improve structural performance in resisting earthquake forces when planning earthquake-resistant high-rise buildings is to use shear walls [7]. Shear wall placement location affects the behavior of high-rise building structures [8]. To meet the required horizontal load, shear walls can be placed appropriately and strategically [4] [9][10][11].
Construction planning for multi-storey buildings must consider design procedures that refer to the SNI 2847: 2019 standard which regulates structural requirements for building-buildings [12], SNI 1726: 2019 which regulates the procedures for earthquake resistance planning for building and non-building structures [13] and SNI 1727:2020 for minimum design loads and related Criteria for buildings and other structures [14].
Shear walls are also designed to minimize damage to non-structural parts [15][16]. SMRFS and shear walls can be combined in structural planning which is often referred to as a dual system [17]. Where two structures with different properties and behaviors are combined and produce a strong structure.
Based on the explanation above, this research is intended to find out how the comparison of planning parameters, structural behavior (displacement and deviation between floors) between the special moment bearing frame system (SMRFS) and dual system.
Theoretical Foundation
Previous studies related to the comparison of SMRFS and dual-system structures found that the addition of shear wall elements affects the robustness of the structural system, where lateral forces due to earthquakes are resisted by shear walls [18]. Analysis result belongs to [11] Placement of shear retaining walls in the center of the building or in the core area of the building has better seismic response, as it effectively attracts lateral loads and reduces vibration response [19]. Research shows that the most effective configuration for shear walls in an 8-story building is to place them around the perimeter and corners of the building. This increases stiffness, reduces torsional effects, and does not disrupt the interior layout of the building.
A. Working Load
SNI 1727:2020 has regulated the minimum loading for building planning, where the loading value is influenced by the function of the space and the building itself. Some types of loads received in buildings are:
- Dead Load
Dead load is the weight of all installed building components including walls, floor coverings, roofs, ceilings, finishes and all architectural aspects that are integral to the building [14].
- Live Load
Live load is the weight that is not fixed or moving that comes from the use and occupants of buildings or other structures that are not included in construction loads or dead loads [14].
- Earthquake Load
Based on SNI 1726:2019 concerning the planning of earthquake-resistant building structures, the earthquake load comes from the movement of the soil layer both horizontally and vertically. It is necessary to analyze the earthquake force based on the dynamic analysis of the earthquake load so that the building can withstand the earthquake load that occurs [13].
B. Earthquake Resistant Structural System
In planning earthquake-resistant structures, there are requirements for the type of structure and Ceismic Design Category (CDC). This category is found in SNI 1726:2019, which is related to the consideration of earthquake hazard level, soil characteristics, occupancy capacity, and function [13]. In the elemental part of the structural frame system used, there are several levels of ordinary, intermediate, and special, which means that the detail requirements and design capacity against structural damage increase at each level according to the expected strength.
Structures with KDS D, E and F are potentially exposed to strong ground vibrations. Based on existing regulations, the seismic load-bearing concrete structural systems applicable to these KDS are SRPMK, special structural walls or a combination of both.
SNI 2847:2019 defines a wall as either a retaining wall or a shear wall. This retaining wall can be interpreted as a wall that supports vertical loads that exceed a certain threshold value [12]. Shear walls are defined as walls, bearing or non-bearing, that are planned to resist earthquake loads that affect the wall plane. A dual-system structure consists of a combination of SMRFS and shear walls [20]. Which is a frame structure capable of withstanding a minimum seismic load of 25% [12].
C. Deviation Between Floor
Drift is lateral movement, which is usually referred to as displacement. Inter-level deviation is a significant parameter to identify the magnitude of, in order to obtain in planning how flexible or rigid the construction structure is. For seismic force-resisting systems consisting of moment frames in structures planned according to seismic design categories D, E, or F, the design inter-storey deviation is (Δ) cannot be greater than Δa/ρ for the entire floor [13]. The calculation uses the following equation:
δx =
Δijin =
Description:
RESEARCH METHODS
D. Buiding Data
Table I is general planning data containing building functions, soil data at the planning location, concrete quality and reinforcing steel quality used. This data is used in the process of taking planning parameters in the standards used.
Table I General Planning Data
No. | Data | Description |
1. | Building Function Type | Hospital |
2. | Planning Location | Sanur Lot H3A, Sanur Kaja, South Denpasar District, Denpasar City, Bali Province |
3. | Total Level | 5 Level |
4. | Building Structure | Reinforced Concrete |
5. | Concrete Quality (fc) | 30 Mpa. |
6. | Quality of stirrup reinforcement (fy) | 420 Mpa. |
7. | Quality of Main Reinforcement (fy) | 420 Mpa. |
8. | Ground Data | Soil search results found the depth of hard soil at 7.2 meter. With average conus resistance at 210 kg/cm2 and the number of sticky barriers at 610 kg/cm. |
E. Research Flow Chart
Figure 1 shows the flow chart of the research to be carried out, the flow chart illustrates the systematic planning of the steps that must be passed from the initial stage to the final stage of the research which results in research conclusions.
Figure 1 Research Flow Chart
F. Planning Data
The dimensional data of the structural components used in modeling the SMRFS and Dual System structures are shown in Table II. Contains information on width and height of beam and column elements, thickness of shear walls and floor slabs used.
Table II Dimensional Data of Structural Components
No. | Component structure | Code | Dimensions of SMRFS | Dual System Dimensions |
(mm) | (mm) | |||
1. | Column | K1 | 700×700 | 600×600 |
K2 | 600×600 | 500×500 | ||
KAA | 450×450 | 400×400 | ||
KL | 500×500 | 400×400 | ||
2. | Blocks | B1 | 300 x 650 | 300 x 450 |
BA1 | 300 x 650 | 250 x 350 | ||
B2 | 300 x 700 | 350 x 500 | ||
BA2 | 300 x 700 | 300 x 450 | ||
B3 | 400 x 650 | 300 x 450 | ||
B4 | 300 x 500 | 200 x 300 | ||
B5 | 400 x 700 | 400 x 700 | ||
BA3 | 250 x 500 | 250 x 500 | ||
B6 | 500 x 1100 | 400 x 750 | ||
B7 | 500 x 700 | 400 x 700 | ||
TB | 250 X 900 | 250 x 900 | ||
3. | Plates. | S1 | 250 | 250 |
S2 | 130 | 130 | ||
S3 | 130 | 130 | ||
S4 | 150 | 150 | ||
S5 | 150 | 150 | ||
S6 | 140 | 140 | ||
4. | Shear Wall | DG | – | 200 |
Figure 2 is the result of drawing the SMRFS structure in ETABS software based on the dimensions of the structure that has been determined. Figure (a) shows the plan form of the planned SMRFS structure and (b) is the result of the planned SMRFS 3D model.
Figure 2 SMRFS Structure Results in ETABS Software
Figure 3 is the result of depicting the Dual System structure in ETABS software based on the predetermined structural dimensions. Figure (a) shows the plan form of the planned dual system structure and (b) is the result of the 3D model of the planned dual system.
Figure 3 Results of Dual System Structure Drawing in ETABS Software
G. Structure Loading
Table III contains details of the dead load adjusting to the provisions stipulated in SNI 1727: 2020 [14]. The dead loads listed in this table include the fixed weight of the building’s structural components, including the value of other structural material components such as walls, floor coverings, mechanical electrical and plumbing dam used in the design and analysis of the structure in order to ensure that the building has the stability to withstand loads throughout its lifetime.
Table III Dead Load
No. | Name | Weight |
1. | Spesi | |
2. | Floor Cover | |
3. | Plafond Gypsum | |
4. | MEP | |
5. | Wall |
Table IV contains details of the live load adjusting the provisions in SNI 1727: 2020 [14]. The live loads contained in this table include temporary loads caused by human activity, tools and other movable items that may change during the use of the building. The magnitude of the load used adjusts to the function of the room being used. Live loads are required to ensure the building remains stable, safe and comfortable for the occupants during the building’s use.
Table IV Live Load
No. | Name | Weight |
1. | Patient Room | 195.78 kg/m2 |
2. | Surgery Room | 292.65 kg/m2 |
3. | Doctor’s Room | 195.78 kg/m2 |
4. | Waiting Room | 488.44 kg/m2 |
5. | Laboratory | 292.65 kg/m2 |
6. | Corridor | 390.55 kg/m2 |
RESULT AND DISCUSSION
H. Earthquake Load
Table V contains the values of the layers and the amount of N SPT, so that the average N value of 27.72 shows that the soil site class is in Medium Soil.
Table V Average N SPT Value
No. | Layer i | Thickness of Layer, in (m) | N value (SPT) | di/Ni |
1. | 1 | 2 | 7 | 0.286 |
2. | 2 | 2 | 15 | 0.133 |
3. | 3 | 2 | 27 | 0.074 |
4. | 4 | 2 | 29 | 0,068 |
5. | 5 | 2 | 30 | 0,066 |
6. | 6 | 2 | 31 | 0,064 |
7. | 7 | 2 | 33 | 0,060 |
8. | 8 | 2 | 42 | 0,047 |
9. | 9 | 2 | 45 | 0,044 |
10. | 10 | 2 | 50 | 0,04 |
11. | 11 | 2 | 50 | 0,04 |
12. | 12 | 2 | 50 | 0,04 |
13. | 13 | 2 | 50 | 0,04 |
14. | 14 | 2 | 50 | 0,04 |
15. | 15 | 2 | 50 | 0,04 |
30 | 1,082 |
Based on the results of the analysis, Table VI is the coefficient presented for earthquake loading on soft soil in accordance with [13] SNI 1726:2019 which contains the design spectra response coefficient in accordance with the risk of hospital buildings with category IV.
Table VI Earthquake Loading Coefficient
No. | Coefficient | Value |
1. | 0.96 | |
2. | 0.39 | |
3. | 1.11 | |
4. | 1.90 | |
5. | 0.71 | |
6. | 0.50 | |
7. | 0.14 second | |
8. | 0.7 second | |
9. | 12 second |
Figure 4 shows the results of the spectrum response design period diagram at the planning location with the site class on soft soil. The response spectrum diagram is obtained from the relationship between the vibration period (T) and the earthquake acceleration (Sa).
Figure 4 Design Response Spectrum
Table VII is the structural ductility factor based on the seismic force-resisting frame system used in the planning. There are over-strength factors, deflection magnification factors, and response modification factors for SMRFS and multiple system structural types.
Table VII Ductility Factor of Structural System
No. | Parameter | SMRFS | Dual System |
1. | (R) | 8 | 7 |
2. | (Ω0) | 3 | 2.5 |
3. | (Cd) | 5.5 | 5.5 |
Table VIII shows the effective weight of the building per floor, this weight is obtained from the building’s own weight, dead weight and live load acting together on the planned building structural components.
Table VIII Effective Building Weight
No. | Lantai | SMRFS | DUAL SYSTEM |
(kg) | (kg) | ||
1. | Roof | 10792.54 | 10779.21 |
2. | Roof Top | 1207731.71 | 1090685.12 |
3. | Third | 1778030.85 | 1628391.61 |
4. | Second | 1827152.86 | 1673874.10 |
5. | First | 1902714.39 | 1752380.53 |
6. | Ground | 2070850.34 | 2044152.20 |
7. | TOTAL | 8797272.72 | 8200262.80 |
Table IX is the result of the earthquake load analysis that contains the seismic response coefficient of earthquake load, earthquake static load, dynamic earthquake force scale and earthquake scale magnification to produce the dynamic earthquake load value (V dynamic) ≥ static earthquake (V static).
Table IX Static and Dynamic Earthquakes
No. | Parameter Lateral | SMRFS | Dual System |
1. | Cs | 0.1341 | 0.1533 |
2. | Vx static | 8666.61 kN | 10612.93 kN |
3. | Vy static | 8169,29 kN | 10224.50 kN |
4. | Initial Scale | 1.838,75 mm/s2 | 2.101.43 mm/s2 |
5. | Magnification Scale | 3313.50 mm/s2 | 3639.78 mm/s2 |
6. | Vx dynamic | 8666.62 kN | 10614.50 kN |
7. | Vy dynamic | 8169.33 kN | 10224.55 kN |
I. Dual System Checking
Based on the standards used, the frame structure in the dual system must be able to withstand at least 25% of the acting earthquake force. Table X results of shear force analysis obtained at the model platform.
Tabel X Dual System Requirements
No. | Shear Force | X-direction | Y-direction |
1. | Dual System | 9071.22 | 6589.19 |
2. | Shear Wall | 6019.49 | 4578.66 |
3. | Percentage of Shear Walls (<75%) | 66.36% | 69.49% |
4. | Frame Percentage (>25%) | 33.64% | 30.51% |
J. Inter-Storey Deviation
Based on the results of the analysis, it is found that the diplascement that occurs in the existing x direction is 25,463 mm and the y direction is 22,905 mm. While the existing structure that is added to the shear wall at the edge of the building in the x direction is 10.035 mm and in the y direction is 17.82 mm. Which is where the existing structure added by the shear wall is stiffer and more effective in supporting the shear force so that it can experience a decrease in deviation of 39% in the x direction and 78% in the y direction compared to the existing structure. Furthermore, the analysis results obtained that the displacement that occurs in the modified structure in the x direction is 16.507 mm and the y direction is 20.508 mm. Which is where the modified structure has an increase in deviation from the existing deviation added to the shear wall at the edge of the building due to the reduction of several structural elements that have been modified where the deviation results obtained do not exceed the specified building permit limit.
Figure 5 Combined X-Direction Deviation
Figure 6 Combined Y-Direction Deviation
CONCLUSIONS
Based on the results of the study, it is concluded that the difference in parameters is earthquake loading, where the value of (R) = 8, (Ω0)= 3, (Cd) = 5,5 for SMRFS and (R) = 7, (Ω0) = 2,5, (Cd) = 5,5 for Dual System. The SRPMK and Dual System structural models meet the requirements of inter-storey deviation values. The results of the comparison between SMRFS (Special Moment Resisting Frame System) and the dual system allow us to determine the right decision in choosing the most appropriate structural system, resulting in a safe, reliable and efficient building.
SUGGESTIONS
The need for further analysis with varying shear wall placements in order to obtain the results of the analysis of the structural behavior of the use of shear walls in a dual system that is more varied and effective in planning.
REFERENCES
- P. P. Chandurkar and P. S. Pajgade, “Post graduate student in structural engineering,” Int. J. Mod. Eng. Res. www.ijmer.com, vol. 3, no. 3, pp. 1805–1810, 2013, [Online]. Available: www.ijmer.com
- Z. Wang, W. Pan, and Z. Zhang, “High-rise modular buildings with innovative precast concrete shear walls as a lateral force resisting system,” Structures, vol. 26, no. April, pp. 39–53, 2020, doi: 10.1016/j.istruc.2020.04.006.
- S. Mustafa, M. Mashaal, O. Shaalan, and M. Khfaga, “Shear Walls against Lateral Load s: A Review,” Egypt. Int. J. Eng. Sci. Technol., vol. 0, no. 0, pp. 0–0, 2022, doi: 10.21608/eijest.2022.128054.1146.
- R. Resmi and S. Yamini Roja, “A REVIEW ON PERFORMANCE OF SHEAR WALL,” Int. J. Appl. Eng. Res., vol. 11, no. I, pp. 369–373, 2016.
- M. Mahdavi, A. Babaafjaei, and S. Hosseini, “A Comprehensive Review on the Structural Performance of Cold-Formed Steel (CFS) Shear Wall,” vol. 8, p. Online, 2023.
- D. Y. Qur’ani and R. Sulaksitaningrum, “Performance and Cost Comparison of Building Structures with SRPM and Shearwall in Seismic Dynamic Analysis,” J. La Multiapp, vol. 6, no. 2, pp. 431–444, 2025, doi: 10.37899/journallamultiapp.v6i2.2046.
- W. Al Agha and N. Umamaheswari, “Analytical study of irregular reinforced concrete building with shear wall and dual Framed-Shear wall system by using Equivalent Static and Response Spectrum Method,” Mater. Today Proc., vol. 43, pp. 2232–2241, 2020, doi: 10.1016/j.matpr.2020.12.525.
- N. Patel and S. Jamle, “Use of Shear Wall Belt at Optimum Height to Increase Lateral Load Handling Capacity in Multistory Building: A Review,” Int. J. Adv. Eng. Res. Sci., vol. 6, no. 4, pp. 310–314, 2019, doi: 10.22161/ijaers.6.4.36.
- H. T. Kalangi, J. Tanijaya, and M. Thetrawan, “Analisis Pengaruh Penempatan Dinding Geser Terhadap Perilaku Dinamik Struktur Bangunan,” Ritektra 2021, no. 2016, p. 14, 2021, [Online]. Available: https://journal.unpar.ac.id/index.php/ritektra/article/view/4921
- H. S. Aji, A. Rosyidah, and J. Saputra, “The effect of variation of shear walls placement on the response of building structure using the Direct Displacement-Based Design method,” Sinergi, vol. 26, no. 2, p. 201, 2022, doi: 10.22441/sinergi.2022.2.009.
- A. Kavani, A. Butala, N. Mehta, and S. Moteriya, “Optimum Location of Shear Wall in RCC Building,” Int. J. Res. Eng. Sci. ISSN, vol. 11, no. April, pp. 251–256, 2023, [Online]. Available: www.ijres.org
- BSN, “SNI 2847-2019 Structural concrete requirements for building structures and explanations,” Sni 03-2874-2019, no. 8, 2019.
- S. 1726, “SNI 1726:2019 Procedures for Earthquake Resistance Planning for Building and Non-Building Structures,” Badan Stand. Nas. Indones., no. 8, p. Herman Kurnianto, D., Teoretis dan Terapan Bidan, 2019.
- “SNI 1727:2020 Minimum design loads and related criteria for buildings and other structures,” Jakarta, no. 8, pp. 1–336, 2020.
- T. A. Ozkul, A. Kurtbeyoglu, M. Borekci, B. Zengin, and A. Kocak, “Effect of shear wall on seismic performance of RC frame buildings,” Eng. Fail. Anal., vol. 100, no. February, pp. 60–75, 2019, doi: 10.1016/j.engfailanal.2019.02.032.
- Y. Sepriawan and P. Pariatmono, “Comparison of Sliding Wall Double System Structure Design Special Moment Bearing Frame (SRPMK) with Basic Insulation System,” Asian J. Eng. Soc. Heal., vol. 3, no. 5, pp. 932–948, 2024, doi: 10.46799/ajesh.v3i5.308.
- A. A. Mondal, G. B. Bhaskar, and D. Telang, “Comparing the Effect of Earthquake on Shear wall building and Non- Shear Wall Building – A Review,” Int. Res. J. Eng. Technol., vol. 4, no. 6, pp. 3286–3289, 2017, [Online]. Available: https://irjet.net/archives/V4/i6/IRJET-V4I6788.pdf
- M. A. Cando, M. A. Hube, P. F. Parra, and C. A. Arteta, “Effect of stiffness on the seismic performance of code-conforming reinforced concrete shear wall buildings,” Eng. Struct., vol. 219, no. July 2019, p. 110724, 2020, doi: 10.1016/j.engstruct.2020.110724.
- L. Teddy and H. H. Tumbelaka, “A Shear Wall Design Study in an 8-Story Building,” vol. 7, no. 2, pp. 61–69, 2025, doi: 10.14710/jadu.v.
- F. Fernando and A. J. Saputra, “Analysis of the Effect of Shear Walls on Building Structural Deviations in High-rise Buildings Monde City Tower M2 Batam City,” J. Civ. Eng. Plan., vol. 3, no. 2, pp. 146–160, 2022, doi: 10.37253/jcep.v3i2.7434.